>vfd article

How to Specify Variable Frequency Drives

Written by Steve Rossiter, President/CEO

There are six important variables to consider when specifying variable frequency drives.


Table of Contents

Load Type for Variable Frequency Drives

Does your variable frequency drive application require a variable torque or constant torque drive?

if the equipment being driven is centrifugal, such as a fan or pump, then a variable torque drive will be more appropriate.

Energy savings are usually the primary motivation for installing variable frequency drives for centrifugal applications, and variable torque drives offer the greatest energy savings.

For example, a fan needs less torque when running at 50% speed than it does when running at full speed. Variable torque operation allows the motor to apply only the torque needed, which results in reduced energy consumption. Conveyors, positive displacement pumps, punch presses, extruders, and other similar type applications require constant level of torque at all speeds. in which case, constant torque variable frequency drives would be more appropriate for the job.

A constant torque drive should have an overload current capacity of 150% or more for one minute. Variable torque variable frequency drives need only an overload current capacity of 120% for one minute since centrifugal applications rarely exceed the rated current. if tight process control is needed, then you may need to utilize a sensorless vector, or flux vector variable frequency drive, which allow a high level of accuracy in controlling speed, torque, and positioning.

Motor information

The following motor information will be needed to select the proper variable frequency drive:

  • Full Load Amp Rating. Using a motor's horsepower is an inaccurate way to size variable frequency drives.
  • Voltage Rating.
  • Speed Range. Generally speaking, a motor should not be run at any less than 20% its specified maximum speed allowed. if it is run at a speed less than this without auxiliary motor cooling, the motor will overheat. Auxiliary motor cooling should be used if the motor must be operated at slow speeds.
  • Multiple Motors. To size a variable frequency drive that will control more than one motor, add together the full-load amp ratings of each of the motors. All motors controlled by a single drive must have an equal voltage rating.
  • Supply Power

    if continuous operation is a must, then the following should be specified:

  • +/- 10% voltage fluctuation
  • +/- 3% frequency variation
  • Voltage sag ride-through for the following:
    • 0% voltage for 1 cycle
    • 60% voltage for 10 cycles
    • 87% voltage continuous

    if you need to supply a 3-phase drive with single-phase power, then the drive must be derated by 25% to 50% of its current-handling ability, which may require you to specify a larger-sized drive.

    Control Methods for Variable Frequency Drives

    With 2-wire control, only one switch is used to run the variable frequency drive. An open switch stops the drive, and a closed switch starts the drive. Two-wire control is predominately used in HVAC applications since t is able to maintain the RUN command to the drive during a loss of power, which enables variable frequency drives to automatically restart when power is restored. Plus, 2-wire control allows drives that have "power loss ride-through" to operate during a power drop that is 2 seconds or less in duration.

    With 3-wire control, two switches are used to run the drive. One switch is needed to stop, and another to start the variable frequency drive. This allows an auxiliary contact from the start to "seal in" the RUN command, just like your more conventional motor starters.

    Speed Reference Alternatives

  • Speed Potentiometer. Allows the operator to set motor speed with pot.
  • Digital Programming / Display Unit. Allows the operator to program and troubleshoot the drive by inputting values through a keypad with an LED or LCD display unit. Drive operation can also be monitored through this display.
  • Analog Signal Follower. 4-20mA or 0-10VDC; must provide variable frequency drives with an isolated input; must use a twisted/shielded pair and keep wire away from 3-phase AC.
  • Selector switch speed selection. Allows operator to select from several preset speeds. Can also be used if the speed is being set via a PLC, and an analog output is not available.
  • Serial Communications. Allow variable frequency drives to communicate on a network, such as MODBUS, PROFiBUS, DEViCENET, or METASYS, enabling drive operation to be coordinated and monitored from a PC.
  • Efficiency and Power Factor

    A drive should have an efficiency rating of 95% or better at full load. Variable frequency drives should also offer a true system power factor of 95% or better across the operational speed range, to avoid penalties from the power utility, save on energy bills, and to protect you equipment (especially motors).

    Protection and Power Quality

  • Motor overload for instantaneous trip and motor over current.
  • Additional Protection: Over voltage, under voltage, over temperature, ground fault, control or microprocessor fault. These protective circuits should provide an orderly shutdown of the VFD, provide indication of the fault condition, and require a manual reset (except under voltage) before restart. Under voltage from a power loss shall be set to automatically restart after return to normal. The history of the previous three faults shall remain in memory for future review.
  • if a built-up system is required. there should also be externally-operated short circuit protection, door-interlocked fused disconnect, circuit breaker or motor circuit protector (MCP) rated at a minimum of 65,000 AiC, and a door-interlocked handle capable of being locked.
  • Harmonics

  • The drive/system should be compliant with iEEE 519-1992. The iEEE 519-1992 Table of Current Distortion Limits for general distribution systems (120V through 69,000V) is given below:
  • Current Distortion Limits for General Distribution Systems
    (120V through 69,000V)

    Maximum Harmonic Current Distortion in Percent of iL

    iSC/iL
    (Load)
    individual Harmonic Order (Odd Harmonics)
    < 11 11 < h < 17 17 < h < 23 23 < h < 35 35 < h TDD
    < 20 4.0 2.0 1.5 0.6 0.5 5.0
    20 < 50 7.0 3.5 2.5 1.0 0.5 8.0
    50 < 100 10.0 4.5 4.0 1.5 0.7 12.0
    100 < 1000 12.0 5.5 5.0 2.0 1.0 15.0
    > 1000 5.0 7.0 6.0 2.5 1.4 20.0
    Contact Us for a Free Quote:

    *Name:

    Company:

    *Email Address:

    *Zip Code:

    *Phone Number:

    Comments or Questions:


    This information will only be used by Energy Management Corporation.


    * required fields

    Latest News
    open house!
    July 26, 2011

    Open House

    Energy Management Corporation will be hosting open houses in both Salt Lake City and Boise. We will have live demonstrations, facility tours, and free food & special product pricing & discounts for those in attendance.

    Come and see what Energy Management Corp is all about:

    Salt Lake City Open House: August 3rd & 4th, 10:00 AM to 4:00 PM
    Boise Open House: August 1st & 2nd, 8:00 AM to 4:00 PM

    Join our team!
    June 26, 2011

    EGSA Certified

    Energy Management Corporation is proud to announce that we are now a member of EGSA—the world’s most prominent organization exclusively dedicated to On-Site Power Generation.

    Learn More about EGSA

    Join our team!
    Jan 24, 2011

    Boise Office Expands

    Energy Management Corporation is proud to now provide our expert motor repair directly in Boise. Our new facility offers all of our motor repair capabilities at our standard expert quality and price.

    Contact our Boise office at 208-322-8100

    FLiR information
    Feb 17, 2011

    FLiR Thermal Cameras Now Available

    Energy Management Corporation is proud to now stock a full line of FLiR Thermal imaging Cameras.

    More about FLiR Cameras